BXCQ Explosion-proof Overflow Static Grounding Control System
2019/07/22

Applied to explosive gas atmosphere Zone 1 & 2; 

◆ Applied to IIA, IIB explosive gas atmosphere; 

◆ Applied to temperature group T1~T6; 

◆ Ambient temperature: -40℃~+60℃; 

◆ Widely used in monitoring and protection in 

petroleum, chemical, gas station, oil depot product 

platform, tank car assembly and disassembly, overflow 

static protector and quantitative loading system 

interlocking control, avoid overflow accident, ensure 

safety static grounding.  

Executive Standard:EN; IEC; GB



  • Performance Features  

    ◆ The controller enclosure is flameproof type, reliable explosion-proof performance. 

    ◆ Static grounding clamp has tank car identification function, ensure its installed on tank car correctly, not other 

    electric conductor, with no-spark type grounding clamp, no-spark produced when equipment impact. 

    ◆ Static grounding clamp has resistance inspection and liquid level monitoring function, provide local and remote audible and visual alarm and interlocking signal for “static” and ''overflow status”, which is convenient for operator to find out problem and avoid overflow accident. 

    ◆ Grounding body resistance has inspection function, ensure reliable grounding of system, when electrostatic 

    grounding is bad or grounding loop resistance >10Ω, provide alarm warning. 

    ◆ With voice and LCD function, the intensity of the sound is 70~120db (the distance is 30cm). 

    ◆ Relay signal output for DCS pump (valve), when grounding is not normal, cut off the operation, audible and 

    visual alarm can still be remote controlled, remind operator the real-time status of on-site grounding. 

    ◆ Red LED shows warning, green LED shows normal working, yellow LED shows standby status. 

    ◆ Grounding clamp uses alloy aiding thimble, with the features of high hardness, good electric conduction, 

    strong breaking paint and rust power, etc. ensure good grounding monitoring device. 

    ◆ Grounding clamp is helix tube shrink design, with the capacities of strength anti-pull, anti-drop, etc. 

    ◆ It can intelligently detect whether the human static voltage is conducted, when the human static voltage is in a 

    dangerous value,sound and light alarm.



  • Type spec. and nameParametersRemark

    BXCQ-YJC

    Explosion-proof OverflowStatic GroundingController

    Ex mark:II 2 G Ex db IIB+H T6 Gb 

                  II 2 D Ex tb IIIC T80℃ Db IP66 

    Protection degree: IP66 

    Response time: <1S 

    Test resistance: <10Ω 

    Working voltage: 220VAC or 24VDC 

    Working current: <20mA 

    Warning method: Interlocking signal and three  

                                 color light instruction 

    Output signal: Relay output, NO NC is optional,  

                           10A 30VDC or 10A 250VAC 

    Enclosure size: 200x300x170 mm 

    Installation dimension: 210x220 mm

    Aluminium alloy enclosure

    BXCQ-JC

    Explosion-proof StaticGrounding Controller

    Ex mark: II 2 G Ex db [ia] IIB+H T6 Gb 

                   II 2 D Ex tb IIIC T80℃ Db IP66 

    Protection degree: IP66 

    Response time: <1S 

    Test resistance: <10Ω 

    Working voltage: 220VAC or 24VDC 

    Working current: <20mA 

    Warning method: sound and light alarm (optional) 

    Output signal: Relay output, NO NC is optional,  

                            10A 30VDC or 10A 250VAC 

    Enclosure size: 200x300x170 mm 

    Installation dimension: 210x220 mm

    Aluminium alloyenclosure

    BXCQ-YC

    Explosion-proofOverflow Controller

    Ex mark: II 2 G Ex db [ia] IIB+H T6 Gb 

                   II 2 D Ex tb IIIC T80℃ Db IP66 

    Protection degree: IP66 

    Response time: <1S 

    Working voltage: 220VAC or 24VDC 

    Working current: <20mA 

    Warning method: Interlocking signal and three  

                                 color light instruction 

    Output signal: Relay output, NO NC is optional  

                           10A 30VDC or 10A 250VAC 

    Enclosure size: 200x300x170 mm 

    Installation dimension: 210x220 mm

    Aluminium alloyenclosure

    BXCQ-JCL

    Explosion-proof Static 

    Grounding Controller

    (dual purposes of manand motor)

     Ex mark:II 2 G Ex db [ia] IIB T6 Gb  

                  II 2 D Ex tb IIIC T80℃ Db IP66

     Protection degree: IP66 

    Response time: <1S 

    Test resistance: <10Ω 

    Working voltage: 220VAC or 24VDC

     Working current: <20mA 

    Warning method: sound and light alarm (optional) 

    Output signal: Relay output, NO NC is optional,  

                            10A 30VDC or 10A 250VAC 

    Touching ball material: Electrostatic subconductor 

    Touching ball diameter: 90mm 

    Enclosure size: 200x300x170 mm 

    Installation dimension: 210x220 mm

    Aluminium alloyenclosure

    BXJ-IIB 

    Series Explosion-proof 

    Junction Box

    Ex mark:II 2 G Ex db IIB+H T6 Gb 2 

                 II 2 D Ex tb IIIC T80℃ Db IP66 

    Protection degree: IP66

    Aluminium alloyenclosure
    Static Grounding Clamp

    Clamp tooth material: Tungsten alloy

    Opening range:Clamp body material: 304 (316 optional)


    Corrosion Resistance 

    Helical Line

    Cable material: Copper wire

    Surface material: PU

    Standard equipment length: 7m

    The length of helical

    Line is customized,

    the max length is 15m

    Homing boardMaterial: 304 stainless steel


  • BXCQ Explosion-proof Overflow Static Grounding Control System  

    (Download here:BXCQ Explosion-proof Overflow Static Grounding Control System.pdf)          


    Contact us for more information:  

    Address : No. 555, Baoqian Road, Jiading District, Shanghai, China  

    Zip Code: 201808  

    Tel: +86 21 39977076 /+86 21 39977076   

    Fax: +86 21 39977077 

    E-mail: gmb@warom.com  